-40%

FLUKE 1735 3 THREE PHASE POWER QUALITY LOGGER ELECTRICAL ENERGY ANALYZER

$ 1581.36

Availability: 100 in stock
  • Product: Power Quality Analyzer
  • All returns accepted: Returns Accepted
  • Brand: Fluke
  • Condition: Used very clean, new battery was installed not too long ago.
  • MPN: 1735
  • Refund will be given as: Money back or replacement (buyer's choice)
  • Return shipping will be paid by: Buyer
  • Restocking Fee: No
  • Item must be returned within: 30 Days

    Description

    SERIOUS BIDDERS ONLY!
    PLEASE READ THE DESCRIPTION CAREFULLY!
    You are bidding on the following:
    *** USED
    ***
    FLUKE 1735 3 THREE PHASE POWER QUALITY LOGGER ELECTRICAL ENERGY ANALYZER
    Item Details:
    Manufacturer:
    FLUKE
    Description:
    Product overview: Fluke 1735 Three-Phase Power Quality Logger
    Power Quality Logging, Electrical Load Studies and Energy Consumption Testing Made Easy
    Fluke’s 1735 Three-Phase power data logger is Fluke's most versatile multi-purpose power quality and energy analyzer on the market for the price and is the ideal power meter for conducting energy studies and basic power quality logging. Set the Power Logger up in seconds with the included flexible current probes and color display. The power quality meter measures most electrical power parameters, harmonics, and captures voltage events.
    Most Common Applications:
    Load studies - verify electrical system capacity before adding loads
    Energy assessments - quantify energy consumption before and after improvements to justify energy saving devices
    Harmonics measurements - uncover harmonic issues that can damage or disrupt critical equipment
    Voltage event capture - monitor for dips and swells that cause spurious resets or nuisance circuit breaker tripping
    Key features
    Record power and associated parameters for up to 45 days
    Monitor maximum power demand over user-defined averaging periods
    Prove the benefit of efficiency improvements with energy consumption tests
    Measure harmonic distortion caused by electronic loads
    Improve reliability by capturing voltage dips and swells from load switching
    Easily confirm instrument setup with color display of waveforms and trends
    Measure all three phases and neutral with included 4 flexible current probes
    View graphs and generate reports with included Power Log software
    Compact, rugged design with IP65 case, 600 V CAT III
    Specifications:
    General
    Display
    ¼ VGA Graphic Color transmissive displays 320 x 240 Pixel with additional background lighting and adjustable contrast, text and graphics in color
    Quality
    Developed, designed and manufactured according to DIN ISO 9001
    Memory
    4 MB Flash memory, 3.5 MB for measuring data
    Interface
    RS-232 SUB-D socket; 115.2 k Baud, 8 data bits, no parity, 1 stop bit, firmware updates are possible with the RS- 232 interface (9-pole extension cable)
    Sample rate
    10.24 kHz
    Line frequency
    50 Hz or 60 Hz, user-selectable, with automatic synchronization
    Power supply
    NiMH battery-pack, with ac adapter (15 V to 20 V / 0.8 A)
    Operation time with battery
    Typical > 12 hours without backlight and > 6 hours with backlight high
    Dimensions
    240 x 180 x 110 mm
    Weight
    1.7 kg, including battery
    Ambient conditions
    Working temperature range
    -10°C to +50°C
    Storage temperature range
    -20°C to +60°C
    Operating temperature range
    0°C to +40°C
    Reference temperature range
    23°C ±2°C
    The above terms are defined in European Standards. To calculate the specification at any point in the working temperature range, use the temperature coefficient below.
    Temperature coefficient
    ±0.1% of the measured value per°C from the reference
    Intrinsic error
    Refers to reference temperature, maximum deviation is guaranteed for two years
    Operating error
    Refers to operating temperature range, maximum deviation is guaranteed for two years
    Climatic class
    C1 (IEC 654-1) -5°C to +45°C, 5% to 95% RH, no dew
    Housing
    Cycoloy shock and scratch proof thermoplast V0-type (non-flammable) with rubber protection holster
    EMC
    Emission
    IEC/EN 61326-1:1997 class B
    Immunity
    IEC/EN 61326-1:1997
    Safety
    Safety
    IEC 61010-1 600 V CAT III, double or reinforced insulation, pollution degree 2
    Protection
    IP65; EN60529 (refers only to the main housing without the battery compartment)
    RMS values are measured with a 20 ms resolution.
    V-rms wye measurement
    Measuring range
    57 V/66 V/110 V/120 V/127 V/220 V/230 V/240 V/260 V/277 V/347 V/380 V/400 V/417 V/480 V AC
    Intrinsic error
    ±(0.2% of measured value + 5 digits)
    Operating error
    ±(0.5% of m. v. + 10 digit)
    Resolution
    0.1 V
    V-rms delta measurement
    Measuring range
    100 V/115 V/190 V/208 V/220 V/380 V/400 V/415 V/450 V/480 V/600 V/660 V/690 V/720 V/830 V AC
    Intrinsic error
    ±(0.2% of m. v. + 5 digit)
    Operating error
    ±(0.5% of m. v. + 10 digit)
    Resolution
    0.1 V
    A-rms measurement
    Flexi set I ranges
    15 A/150 A/3000 A rms (at sine)
    Current clamp ranges
    1 A/10 A
    Resolution
    0.01 A
    Ranges
    150 A/3000 A and 1 A/10 A
    Intrinsic error
    ±(0.5% of m. v. + 10 digit)
    Operating error
    ±(1% of m. v. + 10 digit)
    Ranges
    15 A
    Intrinsic error
    ±(0.5% of m. v. + 20 digit)
    Operating error
    ±(1% of m. v. + 20 digit)
    The errors of the current probes are not considered.
    By using Flexi-set
    Flexi Set measuring error
    ±(2% of m. v. + 10 digit)
    Position influence
    ±(3% of m. v. + 10 digit)
    CF (typical)
    2.83
    When using Flexi Set please make sure to position the conductor opposite to the Flexi Set-lock
    Power measurement (P - Active, S - Apparent, Q- Reactive, D - Distorting
    Measuring range
    see V rms and A rms measurement
    Power errors are calculated by adding the errors of voltage and current
    Additional error due to power factor PF
    Specified error x (1-[PF])
    Maximum range with voltage range 830 V delta-connection and 3000 A current range is 2.490 MW, higher displayed values possible when using PTs and CTs with ratio feature
    Intrinsic error
    ±(0.7% of m.v. +15 digit)
    Resolution
    1 kW
    Operating error
    ±(1.5% of m.v. + 20 digit)
    Typical range with voltage range 230 V wye connection and 150 A current range is 34.50 KW.
    Intrinsic error
    ±(0.7% of m.v. +15 digit)
    Resolution
    1 W to 10 W
    Operating error
    ±(1.5% of m.v. + 20 digit)
    The errors of the current sensors themselves have not been considered.
    Energy measurement (kWh, KVAh, kVARh)
    Intrinsic error
    ±(0.7% of m.v.+ F variation error* + 15 digit)
    Resolution
    1 W to 10 W
    Operating error
    ±(1.5% of m.v. + F variation error1 + 20 digit)
    1. Frequency variation error
    PF (Power factor)
    Range
    0.000 to 1.000
    Resolution
    0.001
    Accuracy
    ±1% of full scale
    Frequency measurement
    Measuring range
    46 Hz to 54 Hz and 56 Hz to 64 Hz
    Intrinsic error
    ±(0.2% of m. v. + 5 digit)
    Operating error
    ±(0.5% of m. v.+ 10 digit)
    Resolution
    0.01 Hz
    Harmonics
    Measuring range
    To 50th harmonic (< 50% of nom)
    Accuracy
    Vm, Im, THDV, THDI
    IEC 61000-4-7:2002, Class II
    Vm ≥ 3% Vn
    ±5% Vm
    Vm < 3% Vnom
    ±0.15% Vnom
    Im ≥ 10% Inom
    ±5% Im
    Im < 10% Inom
    ±0 5% Inom
    THDV
    for THD < 3% ±0.15% at Vnom
    for THD ≥ 3% ±5% at Vnom
    THDI
    for THD < 10% ±0.5% at Inom
    for THD ≥ 10% ±5% at Inom
    Vnom
    Normal voltage range
    Inom
    Nominal current range
    Vm and Im are measured values of harmonic m
    Events
    Detection of voltage dips, voltage swells and voltage interruptions with a 10 ms resolution and measuring error of the half period sine wave of rms.
    Intrinsic error
    ±(1% of m.v. + 10 digit)
    Operating error
    ±(2% of m.v. + 10 digit)
    Resolution
    0.1 V
    Condition:
    USED
    Auction Details:
    Shipping:
    All
    domestic
    packages will be shipped out via Fedex, UPS, or USPS within the lower 48 states
    Shipping to Hawaii and Alaska would be extra, and those shipments will be shipped out via USPS priority mail, unless otherwise stated in the auction or negotiated in emails.
    Shipping to APO, RR, or PO box will be handled via USPS and would be extra on certain items, please email us prior bidding.
    Goods will be dispatched the latest in
    2
    business days.
    Goods will be shipped out after the holidays and weekends.
    No local pick
    ups accepted at this time, unless otherwise stated in the auction
    Shipping costs are set at that price to cover some of our costs and packaging and handling fees as well as some of the ebay and paypal fees which add to about 13% of the total end price. Please don't email us to negotiate about the shipping costs.  We are extremely busy, so we might not answer your emails.
    Shipping and handling fees are not negotiable, by bidding on this item the buyer agrees to pay for all the shipping costs
    We ship to any destination in the world.
    INTERNATIONAL BUYERS:
    The International shipping rate is flat rate to most destinations in the world, please email us for additional information.
    California buyers are subject to pay 9% tax.
    International  buyers are responsible for all tax and custom duty charges outside the country.
    Payment:
    U.S. Buyers:
    Credit cards through PayPal
    Please note that we can't accept direct credit card payments at this time
    International Buyers:
    PayPal or Wire
    Payment is due within 6 days of auction closing.
    If payment is not received within this time unless otherwise stated or negotiated, item will be relisted on eBay.
    Terms & Conditions:
    After the auction is closed,
    auction winners should contact us regarding any questions or requests.
    After the auction is closed, payment should be received within 6 days.
    Buyer has 14 days to return the product, return product should be brand new with all original accessories, buyer pays shipping costs both ways.
    Shipping and handling charges are not returnable
    Items will be replaced or exchanged in case of DOA
    If the same item or similar item is not in stock in case of DOA, the buyer will receive a refund back
    We combine shipping to save customers money, however, there will be an additional charge per item, please read the description for each item to find out about the specific fees.
    All buyers are subject to pay all taxes and duty fees inside and outside of the United States,
    Our facilities are closed during the weekends and other holidays and there will be no shipments during these time periods. All packages will go out after the weekend or after the holidays.
    Contact Information:
    Please use ebay message